YBW-40.5 Prefabricated Substation

YBW-40.5 Prefabricated Substation

This series of prefabricated substation is a type of outdoor complete equipment with high voltage 40.5kV, low voltage 12kV (0.4kV), transformer capacity 800~20000kVA, frequency 50Hz and three-phase AC system, including 40.5kV main transformer box, 40.5kV switch box and 12kV (0.4kV) switch box. Boxes are connected with each other by cables, and 12kV (0.4kV) incoming and outgoing lines are all connected by cables. This substation is a new generation product to satisfy urban and rural power grids construction. It takes the role of receiving, converting and distributing electric energies, and features small volume, high completeness, easy installation, movability, low cost and safe operation.

Working conditions:
1. Altitude: ≤1000m (using plateau type design if >1000m)
2. Ambient temperature: -25℃ ~ +40℃
3. Wind speed: ≤34m/s (wind pressure ≤700pa)
4. Icing thickness: ≤20mm
5. Pollution grade: Ⅱ, Ⅲ
6. IP code: IP23
7. Relative humidity: ≤85%
8. Natural ventilation area: 5m2
9. Installation site: no fire, explosion, severe pollution, chemical corrosion or severe vibration, and gradient: ≤5°
10. Normal use on ground, or on the buildings that has less than 10m of height and can bear 60 tons of pressure
Remark: please consult us if you demand other different conditions

Technical parameters:

Items
Units
High Voltage Unit
Transformer
Low Voltage Unit
40.5kV
12kV
JYN, XGN, KYN
KYN28, XGN2, HXGN
SZ11, S11, SC
Rated Voltage
kV
40.5
12
35/10-04.
0.4
Rated Capacity
kVA
≤20000
Mode of Wiring
Y, d11
Insulation Grade
Grade
F
Insulation System Temperature Limit
℃
155
Temperature Rise Limit
K
100
Rated Current (Main) Loop
A
400-1600
630-2000
Rated Short Circuit Breaking Current
25
31.5
Rated Short Circuit Making Current
kA
63
80
4s Rated Short Time Withstand Current
kA
25
31.5
Rated Peak Withstand Current
kA
63
80
Power Frequency Withstand Voltage
kV
95/118
42/48
85
2.0/2.5
Lightning Impulse Withstand Voltage
kV
185/215
75/85
185
8
Acoustic Level
dB
<55
IP Code
Front and four sides: IP43, ventilation part of top cover and bottom inside the box: ≥ IP23 (transformer placed in the open air: IP00)