SDKW1L residual-current circuit breaker is used for distribution networks with frequency 50Hz, rated voltage AC400V and rated current 800A and below. It can protect human bodies against indirect contact and avoid fire disasters if insulation destruction brings about earthing fault current. It can distribute electric energy, protect circuits, and keep electrical power units from overload and shot circuit. It takes the role of infrequent turn-on and turn-off and infrequent motor start-up. Rated residual operating current I△n and maximum breaking time can be adjusted on site according to actual conditions. If residual current occurs, we can customize a function of alarming, but no tripping.
This series of breaker conforms to standards of IEC60947-2 and GB14048.2.
|
Model
|
SDKW1L-100
|
SDKW1L-225
|
SDKW1L-400
|
SDKW1L-630, 800
|
|||||||||||
|
Frame Size Rated Current (Inm)(A)
|
100
|
225
|
400
|
630, 800
|
|||||||||||
|
Rated Current (In)(A)
|
10, 16, 20, 25, 32
|
100, 125, 140, 160
|
225, 315
|
400, 500, 630
|
|||||||||||
|
40, 50, 63, 80, 100
|
180, 200, 225
|
350, 400
|
700, 800
|
||||||||||||
|
Number of Poles
|
2
|
3
|
4
|
2
|
3
|
4
|
3
|
4
|
3
|
4
|
|||||
|
Rated Insulation Voltage (Ui)(V)
|
AC800
|
||||||||||||||
|
Rated Working Voltage (Ue)(V)
|
AC400
|
||||||||||||||
|
Rated Impulse Withstand Voltage (Uimp)(V)
|
8000
|
||||||||||||||
|
Flashover Distance
|
50
|
100
|
|||||||||||||
|
Breaking Capacity Level
|
L
|
M
|
H
|
L
|
M
|
H
|
L
|
M
|
H
|
L
|
M
|
H
|
|||
|
Ultimate Short Circuit Breaking Capacity
(Icu)(kA) |
30
|
50
|
85
|
30
|
50
|
85
|
50
|
65
|
100
|
50
|
65
|
100
|
|||
|
Service Short Circuit Breaking Capacity
(Ics)(kA) |
15
|
35
|
50
|
15
|
35
|
50
|
35
|
42
|
65
|
35
|
42
|
65
|
|||
|
Rated Residual Short Circuit Making (Breaking) Capacity
|
8.75
|
12.5
|
21
|
8.75
|
12.5
|
21
|
12.5
|
13.5
|
25
|
12.5
|
13.5
|
25
|
|||
|
Rated Residual Operating Current (I△n)(mA)
|
No delay
|
30/100/500, 100/300/500
|
30/100/500, 100/300/500
|
100/300/500
|
300/500/1000
|
||||||||||
|
Delay
|
100/300/500
|
100/300/500
|
100/300/500
|
300/500/1000
|
|||||||||||
|
Rated Residual Non-operating Current
(I△n)(mA) |
1/21△n
|
1/21△n
|
1/21△n
|
1/21△n
|
|||||||||||
|
Operating Performance (Number of Times)
|
Switch on
|
1500
|
1000
|
1000
|
1000
|
||||||||||
|
Switch off
|
8500
|
7000
|
4000
|
4000
|
|||||||||||
|
Total
|
10000
|
80000
|
5000
|
5000
|
|||||||||||
|
Residual Current Operating Time of Protection
|
I△n
|
2I△n
|
5I△n
|
10I△n
|
|||||||||||
|
Maximum Breaking Time (S)
|
No delay
|
0.2
|
0.1
|
0.04
|
0.04
|
||||||||||
|
Delay
|
0.5/1.15/2.15
|
0.35/1/2
|
0.25/0.9/1.9
|
0.25/0.9/1.9
|
|||||||||||