HXGN-12 AC Metal Insulation-Enclosed Ring Main Unit Switchgear

HXGN-12 AC Metal Insulation-Enclosed Ring Main Unit Switchgear

It is a kind of metal insulation-enclosed switchgear with vacuum load switch or sulfur hexafluoride load switch (or pressure-operated load switch). It is a new generation high voltage electric equipment, applicable for construction or renovation of urban and rural power grids. This series of switchgear is oil-free and non-toxic, with beautiful exterior, reliable anti-misoperation mechanical interlock, small volume, light weight and easy operation. It realizes both manual and power-driven opening and closing, which guarantees safe use, convenient maintenance and reliable and stable quality. Furthermore, it can be installed against the wall because of its small volume.

Working conditions:
1. Ambient temperature: +40°C~-25°C; 24h average temperature: ≤ 35°C
2. Altitude: ≤1000m
3. Gradient: ≤3°
4. No dust, or no corrosive or inflammable gas, vapor or salt mist
5. Earthquake horizontal acceleration: ≤3g
6. Please consult us if clients have other different conditions

Vacuum load switch technical parameters:

Items Units Load Switch “Load Switch + Fuse Protector” Combined Device
Rated Voltage kV 12 12
Rated Current A 630 125
Rated Active Load Breaking Current,
Rated Closed Loop Breaking Current
A 630
Rated Short Time Withstand Current (4S) kA 20
Rated Short Circuit Making Current kA 50
Rated Peak Withstand Current kA 50
Rated Cable Charging Breaking Current A 10
Rated Breaking No-Load Transformer kVA 1600 1600
Rated Breaking Take-Over Current A 2000
Rated Short Circuit Breaking Current of Fuse Protector kA 31.5 (Expected Value)
1min Power Frequency Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) kV 42/48 42/48
Lightning Impulse Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) kV 75/85 75/85
Mechanical Life Number of Times 5000 5000
Electric Operation Voltage V AC/DC 220V
Rated Voltage of Shunt Release V AC/DC 220V

Pressure-operated load switch technical parameters:

Items Units Load Switch “Load Switch + Fuse Protector” Combined Device
Rated Voltage kV 12 12
Rated Current A 630 125
Rated Active Load Breaking Current,
Rated Closed Loop Breaking Current
A 630
Rated Short Time Withstand Current (4S) kA 20
Rated Short Circuit Making Current kA 50
Rated Peak Withstand Current kA 50
Rated Cable Charging Breaking Current A 10
Rated Breaking No-Load Transformer kVA 1250 1250
Rated Breaking Take-Over Current A 1700
Rated Short Circuit Breaking Current of Fuse Protector kA 31.5 (Expected Value)
1min Power Frequency Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) kV 42/48 42/48
Lightning Impulse Withstand Voltage (Phase to Phase, Phase to Ground /Breaking) kV 75/85 75/85
Mechanical Life Number of Times 2000 2000
Sulfur hexafluoride load switch technical parameters:

Items Units Values
Rated Voltage kV 12
Rated Current A 630
Rated Frequency Hz 50
Rated Short Time Withstand Current kA 20
Rated Short Circuit Duration Time S 4
Rated Peak Withstand Current kA 50
Rated Short Circuit Duration Time of Earthing Switch S 4
Rated Peak Withstand Current of Earthing Switch kA 50
Rated Insulation Level 1min Power Frequency Withstand Voltage (Valid Value) kV (Phase to Phase, Phase to Ground) 42; (Breaking) 48
Lightning Impulse Withstand Voltage (Peak Value) kV (Phase to Phase, Phase to Ground) 75; (Breaking) 85
Rated Pressure of SF6 Gas (meter value at 20°C) Mpa 0.04
Leak Rate of SF6 Gas 1%
IP Code IP3X