This series of prefabricated substation is a type of outdoor complete equipment with high voltage 40.5kV, low voltage 12kV (0.4kV), transformer capacity 800~20000kVA, frequency 50Hz and three-phase AC system, including 40.5kV main transformer box, 40.5kV switch box and 12kV (0.4kV) switch box. Boxes are connected with each other by cables, and 12kV (0.4kV) incoming and outgoing lines are all connected by cables. This substation is a new generation product to satisfy urban and rural power grids construction. It takes the role of receiving, converting and distributing electric energies, and features small volume, high completeness, easy installation, movability, low cost and safe operation.
Working conditions:
1. Altitude: ≤1000m (using plateau type design if >1000m)
2. Ambient temperature: -25℃ ~ +40℃
3. Wind speed: ≤34m/s (wind pressure ≤700pa)
4. Icing thickness: ≤20mm
5. Pollution grade: Ⅱ, Ⅲ
6. IP code: IP23
7. Relative humidity: ≤85%
8. Natural ventilation area: 5m2
9. Installation site: no fire, explosion, severe pollution, chemical corrosion or severe vibration, and gradient: ≤5°
10. Normal use on ground, or on the buildings that has less than 10m of height and can bear 60 tons of pressure
Remark: please consult us if you demand other different conditions
Technical parameters:
|
Items
|
Units
|
High Voltage Unit
|
Transformer
|
Low Voltage Unit
|
|
|
40.5kV
|
12kV
|
||||
|
JYN, XGN, KYN
|
KYN28, XGN2, HXGN
|
SZ11, S11, SC
|
|||
|
Rated Voltage
|
kV
|
40.5
|
12
|
35/10-04.
|
0.4
|
|
Rated Capacity
|
kVA
|
≤20000
|
|||
|
Mode of Wiring
|
Y, d11
|
||||
|
Insulation Grade
|
Grade
|
F
|
|||
|
Insulation System Temperature Limit
|
℃
|
155
|
|||
|
Temperature Rise Limit
|
K
|
100
|
|||
|
Rated Current (Main) Loop
|
A
|
400-1600
|
630-2000
|
||
|
Rated Short Circuit Breaking Current
|
25
|
31.5
|
|||
|
Rated Short Circuit Making Current
|
kA
|
63
|
80
|
||
|
4s Rated Short Time Withstand Current
|
kA
|
25
|
31.5
|
||
|
Rated Peak Withstand Current
|
kA
|
63
|
80
|
||
|
Power Frequency Withstand Voltage
|
kV
|
95/118
|
42/48
|
85
|
2.0/2.5
|
|
Lightning Impulse Withstand Voltage
|
kV
|
185/215
|
75/85
|
185
|
8
|
|
Acoustic Level
|
dB
|
<55
|
|||
|
IP Code
|
Front and four sides: IP43, ventilation part of top cover and bottom inside the box: ≥ IP23 (transformer placed in the open air: IP00)
|
||||