Sub-section post takes the switching function, to distribute power and link the power source and distribution network. It is the extension of power source busbar, which increases the number of power source. The application of sub-section post solves several problems, such as lack of outgoing lines of substation and restriction of outgoing line corridor. It reduces the investment and upgrades the structure of power grid.
Working Conditions:
1. Altitude: ≤1000m
2. Maximum ambient temperature: + 40℃
3. Minimum ambient temperature: -25℃
4. Maximum daily temperature difference: 25K
5. Indoor humidity: daily average ≤95%, monthly average ≤90%
6. Earthquake resistance: horizontal acceleration 0.2g, vertical acceleration 0.1g, applied simultaneously; using resonance, sine and beat wave test method; exciting 5 times every 2s, 5 waves per time, safety factor ≥1.67
7. No gas, vapor, chemical deposit, dust or pollution that might affect the insulation of load switch; no explosive or corrosive medium
8. Applicable for unearthed system, or 10kV system earthed through low resistance or arc suppression coil
Technical Parameters:
| No. | Items | Units | Values | ||
| Load Switch | Combined Devices | ||||
| 1 | Rated Voltage | kV | 12 | ||
| 2 | Rated Frequency | Hz | 50 | ||
| 3 | Rated Current | A | 630 | 200 | |
| 4 | Rated Load Breaking Current | A | 630 | 630 | |
| 5 | Rated Short Time Withstand Current (Valid Value) | kA | 20kA | ||
| 6 | Rated Short Circuit Duration Time | s | 3s | ||
| 7 | Rated Peak Withstand Current | kA | 50 / 63 | ||
| 8 | Closed Loop Breaking Current | A | 630 | ||
| 9 | Rated Cable Charging Breaking Current | A | 25 | ||
| 10 | Rated No-Load Transformer Breaking Current | A | 16 | ||
| 11 | Rated Breaking Transfer Current | A | 1750 | ||
| 12 | Prospective Short Circuit Breaking Current of Fuse Protector (Valid Value) | kA | 63 | ||
| 13 | Earthing Switch Short Time Withstand Current /Duration Time | kA | 25kA/1s | ||
| 14 | Rated Current Breaking Times | Number of Times | ≥200 | ||
| 15 | Mechanical Life | Number of Times | ≥2000 | ||
| 16 | Annual Leak Rate of SF6 Gas | ≤1% | |||
| 17 | 1min Power Frequency Withstand Voltage (Valid Value) | Breaking | kV | 48 | |
| Phase to Phase | kV | 42 | |||
| Phase to Ground | kV | 42 | |||
| Lightning Impulse Withstand Voltage (Peak Value) | Breaking | kV | 85 | ||
| Phase to Phase | kV | 75 | |||
| Phase to Ground | kV | 75 | |||
| 18 | Spring Operating Mechanism | Manual, or upgraded to electric | |||
| 19 | Operating Voltage | V | DC 48V/ AC 220V | ||
| 21 | External Insulation Creepage Distance | mm/kV | ≥20 | ||
| 22 | Non-Simultaneity While Opening | ms | <5 | ||
| 23 | Non-Simultaneity While Closing | ms | <5 | ||
| 24 | Major Loop Resistance | uΩ | <140 | ||
| 25 | IP Code of Cabinet Shell | IP4X | |||